What is SOV(solenoid valve) in Control Valve 

Solenoid valves are often used in applications where a control valve is required to be actuated quickly to a fault position under certain conditions. It is generally designed to be in the air supply line and is an important accessory to the air control system.
Table of Contents
    Add a header to begin generating the table of contents

    With the upgrade of automation, the application of solenoid valves in control valves is becoming more and more common, we can see not only butterfly type control valves, ball type control valves equipped with solenoid valves, but many globe type control valves also installed solenoid valves. For the improvement of process requirements, we need to understand the function and role of the solenoid valve once again.

    solenoid valve in control valve
    solenoid valve in control valve

    What is SOV(solenoid valve)

    Solenoid valves are often used in applications where a control valve is required to be actuated quickly to a fault position under certain conditions. It is generally designed to be in the air supply line and is an important accessory to the air control system. The signal from the solenoid valve controls the action of the internal valve assembly, allowing flow through the valve in one position and isolating or venting air in the other.

    sov in globe control valve
    sov in globe control valve

    Why is a Single SOV required on a Control Valve?

    single solenoid valve in control valve
    single solenoid valve in control valve

    For example in the case, if a control valve has to be quickly opened in an emergency, a two-way SOV is fitted between the output port of the positioner and the inlet port of the actuator.

    When the SOV is activated, the inlet port of the solenoid valve is linked to the outlet, enabling air to flow from the positioner output to the actuator.

    The output of the SOV is connected to the exhaust port when it is de-energized, quickly venting air into the control valve to move it to the fail-safe position.

    Why Dual SOV on a Control Valve Is Required?

    dual solenoid valve in control valve
    dual solenoid valve in control valve

    Due to a single solenoid valve for the control valve process, in special failures, such as solenoid valve coil open circuit, blown fuse, plunger stuck, etc. lead to the failure of a single solenoid valve, which eventually leads to some unnecessary process disruption and significant losses due to the plant’s inability to close/open the control valve at the important position.

    So for the purpose of redundancy, the dual solenoid valve design process is used on special and important occasions.

    Dual Solenoid Valve Circuits

    In the figure below, a dual SOV pneumatic schematic is shown.

    double solenoid valves 1

    Consider that the actuator receives air constantly under typical circumstances.

    The positioner output is linked to both SOV inlets, the SOV-1 outlet is connected to the SOV-2 exhaust, and the actuator receives the final output from the SOV-2.

    • Solenoid Valve-1 SOV-1 Failure

    If SOV-1 fails, the SOV-1 output port is linked to the exhaust, and the air is leaving SOV-2 since SOV-2 is powered and the inlet is connected to the output.

    sov 1 failure 1
    sov 1 failure

    Air Flow indicators are depicted with arrows in the illustration above.

    • Solenoid Valve-2 SOV-2 Failure

    If SOV-2 becomes failure then the SOV-2 outlet is connected to the exhaust and SOV-1 is energized then the air goes from the SOV-1 inlet to the outlet then the outlet is connected to the SOV-2 exhaust which is connected with the SOV-2 outlet in fail condition and the air is going to actuator.

    sov 2 failure 1
    sov 2 failure

    Air Flow indications are shown in the above figure with the arrows.

    • Solenoid Valve-2 SOV-1 and SOV-2 Both Failure

    If SOV-2 fails, then the SOV-2 outlet is connected to the exhaust and SOV-1 is powered. The air then flows from the inlet port of SOV-1 to the outlet, which is connected to the SOV-2 outlet in the fail state.

    sov 1 and sov 2 both failure 1
    sov 1 and sov 2 both failure

    Air Flow indicators are depicted with arrows in the illustration above.

    How to Evaluate the SOV Quality and Stability of an Operating Plant

     Utilize a pyrometer to determine the SOV’s monthly surface temperature. The surface temperature is nearly comparable if both SOVs are manufactured by the same company. (Maximum difference between both SOV is 5 degrees Celsius.) Check the coil resistance if the temperature differential is greater.

    Physically inspect the exhaust port to make sure it is not jammed and is operating normally.

    Case Study: Control Valve With the Interlock Shut-off Function

    Question: Does this control valve with the interlock shut-off function in the picture have to be implemented with a solenoid valve in front of the positioner? Why can’t it be implemented in the DCS program? For example, set up a signal in the DCS to give the control valve a full open or full close when the interlock is triggered. 

    sov in control valve
    sov in control valve

    Answer: Control valve with interlocking shut-off function requirements, need to install a solenoid valve in the front of the positioner. The following 3 reasons are for your reference. 

    1. The positioner sometimes acts relatively slowly (the positioner output is usually a constant value, and the diaphragm actuator of the control valve varies in size), which does not meet the “fast response” requirement.

    2. The positioner input signal – valve position relationship is often not very accurate, and when the deviation is not significant, it does not affect the operation of the system and is not detected (the actual maintenance often encountered when the positioner needs to be adjusted when during maintenance), so the control signal through the positioner to achieve the control valve shutdown is not necessarily reliable.

    3. The reliability of the safety interlock requires that the interlocking action signal and the fault signal are consistent (the action signal of the interlocking signal is in the same form and the performance of the lost signal line), while the closing signal of the positioner is 4mA or 20mA, which cannot meet this requirement.

    The above analysis is not necessarily comprehensive, but the interlocking system to achieve the required control room power failure or control room to the control valve signal wire failure (eg: bridge break) when the control valve can ensure shutdown, but also must have universal guidance (to form a specification), “control valve with interlock shutdown, must be between the control valve and the positioner install a solenoid valve to achieve” has become the principle to observe.

    • HGT-20507 in the provisions of 11.9.3 solenoid valve selection should meet the following requirements: for remote control, process control, and interlocking systems, to achieve automatic closure of the air supply system, so that the control valve open or closed occasions.
    • SHT3005 remote control, process control, and interlocking systems, to achieve automatic shutdown of the air supply system, control valve switching and other occasions, which should be selected for low power (less than 4W) three-way or four-way solenoid valve. The low-power solenoid valve may not be suitable for special control valves.
    • The company’s corporate standards: If the control valve as the final component of the SIS interlock that has SIL level requirements, it needs to have solenoid valve action, while the corresponding controller with manual, given the corresponding output. In general, the control valve of DCS interlocking action without SIL level requirements does not require a solenoid valve, the action will correspond to the controller with manual, given the corresponding output.

    Combined with the specifications and company requirements, against P&ID practices, the configuration of solenoid valves is recommended as follows.

    1) Control valves participating in IPL (whether DCS or SIS) interlocking, should be equipped with solenoid valves.

    (2) in the control valve on the pipeline without a shut-off valve, and the process that the operation interlocking requirements are relatively high (solenoid valve can be understood as a switch for the light, 4-20mA for the light knob), can be considered with solenoid valve.

    Contact Us

    With expertise in valves and rich experience in the oil&gas, chemical industry, textile mills, power plants, and sugar mills. THINKTANK has become the premier manufacturer of next-generation precision control valves.

    With a customer base that includes over 42 of the world’s leading engineering&contractors and international valve brands, THINKTANK Valves offers cost-effective valves that help our customers achieve automated process control without paying high prices.

    Facebook
    Twitter
    LinkedIn
    Pinterest
    Print
    solenoid valve in control valve

    What is SOV(solenoid valve) in Control Valve 

    Solenoid valves are often used in applications where a control valve is required to be actuated quickly to a fault position under certain conditions. It is generally designed to be in the air supply line and is an important accessory to the air control system.

    Read More
    diesel generators

    Fusible Link Valves For Diesel Generators

    The fusing link valve for the diesel generator set includes the valve body and actuator, and the valve body and actuator are fixed by a fixed bracket/yoke. The actuator of the fused valve includes the shaft, fusible link, manual/gear operator, actuator protection cover, limit switch, etc.

    Read More
    sluice gate valve

    Sluice Gate Valve 101

    The sluice gate valves are real end-of-line valves designed to hold back water with minimal leakage in applications such as drains, sump tanks, and distribution boxes.

    Read More
    condensate recovery system

    Condensate Return System

    Condensate has a large amount of heat, generally accounting for about 20-30% of the total heat of steam, and for some equipment, it can be as high as 40%.  Therefore, if high-temperature condensate can be recycled as boiler make-up water or used for secondary flash steam, it not only saves industrial water but also saves a large amount of fuel.

    Read More
    three way control valves

    Water Mixing

    Water mixing is the mixing of water at different temperatures, and the resulting mixing temperature varies at different hot and cold flows

    Read More
    uni directional knife gate valve manufacturer

    Knife Gate Valve 101

    Knife gate valves are primarily made for isolation and on-off services in systems with high suspended particle contents. Knife gate valves are particularly useful for managing viscous, corrosive, and abrasive media in addition to the slurry.

    Read More
    Joy Preview

    A good partner is a lasting and effective investment

    Focused on Control Valves & Self-Operated Pressure Regulators For Over 10 Years

    Grow Your Business is Our Top Priority. Contact Now You Will Get More Than You Expect.

    Joy Preview

    ASK FOR QUOTE

    Just leave your name, email, and simple message or requirements, We will contact you within 1 hour.

    WhatsApp: +86 185 1656 9221

    Skype ID: sowell85

    Wechat ID: +86 189 5813 8289