Share optimized solutions, professional valve knowledge and industry news

Please enter the relevant terms or keywords you need to consult, and relevant articles will appear in the search results. If you can’t find the answer you need, please feel free to contact us and we will be happy to help. Or you can directly send an email to [email protected]

ABB Positioner TZIDC Auto Calibration Quick Guide

Table of Contents

This guide explains how to configure and automatically calibrate an ABB TZIDC or TZIDC-200 digital valve positioner using the local four-button interface.

abb positioner tzidc auto calibration quick guide
abb positioner tzidc auto calibration quick guide

Button Functions

ButtonFunction
ENTERConfirm a selection, start an action or save a setting
MODESelect an operating mode, parameter group or parameter
▲ UPMove upward through the menu or increase a value
▼ DOWNMove downward through the menu or decrease a value

On the configuration level, hold MODE and press the arrow buttons to move between parameters. To select another parameter group, hold MODE + ENTER and press ▲ or ▼.

Before Calibration

Confirm that:

  • The positioner is correctly mounted.
  • The feedback lever or rotary coupling is correctly installed.
  • The position feedback shaft remains within its permitted operating range.
  • Pneumatic tubing is connected correctly.
  • Clean instrument air is available.
  • The electrical signal is connected.
  • The valve can safely travel through its full stroke.

For linear actuators, the usable feedback span must remain within the positioner’s linear operating range. For rotary actuators, the normal usable feedback span is 90°.

Warning: Auto Adjust moves the valve through its operating range. Isolate the valve from the process before starting calibration.

Auto Calibration Procedure

StepProcedure
1. Enter Configuration ModePress and hold ▲ and ▼ simultaneously. Briefly press and release ENTER while continuing to hold both arrow buttons. Wait until the countdown changes from 3 to 0, then release the arrow buttons. The display enters configuration mode at P1.0 ACTUATOR.
2. Select the Actuator TypeAt P1.0 ACTUATOR, use ▲ or ▼ to select LINEAR for a linear actuator or ROTARY for a rotary actuator.
3. Select Full Auto AdjustHold MODE and press until P1.2 ADJ_MODE appears. Release MODE, then select FULL.
4. Open Auto AdjustHold MODE and use ▲ or ▼ to select P1.1 AUTO_ADJ. Release MODE.
5. Start Auto AdjustPress and hold ENTER until the countdown changes from 3 to 0. Release ENTER to start calibration.
6. Wait for CompletionThe display shows RUN together with the current calibration step. Do not interrupt the signal or air supply.
7. Confirm the ResultWhen COMPLETE appears, press ENTER to acknowledge the message.
8. Save and ExitMove to P1.4 EXIT. Select NV_SAVE, then hold ENTER until the countdown reaches 0. The positioner saves the settings and returns to the operating level.
9. Verify Valve OperationApply 4, 8, 12, 16 and 20 mA signals. Confirm the valve direction, displayed position and full travel.

Entering configuration mode requires both arrow buttons to remain pressed until the countdown has finished. In P1.1 AUTO_ADJ, holding ENTER through the countdown starts the selected calibration mode. Settings are permanently stored by leaving the configuration level through EXIT → NV_SAVE.

P1.0 Actuator Type

SettingApplication
LINEARGlobe valves and other linear-stroke actuators using a feedback lever
ROTARYBall valves, butterfly valves and other part-turn actuators using rotary feedback

The setting configures the positioner for the appropriate position-sensor range. ABB specifies approximately ±30° for the linear setting and ±45° for the rotary setting. Run Auto Adjust again whenever the actuator type is changed.

LINEAR and ROTARY describe the actuator and feedback arrangement. They do not determine whether the valve is fail-open or fail-close.

P1.2 Auto Adjust Mode

For initial commissioning, select:

P1.2 ADJ_MODE = FULL

SettingFunction
FULLComplete calibration
STROKEDetermines the end positions and stroke only
CTRL_PARDetermines the control parameters only
ZERO_POSCalibrates the zero position only
LOCKEDAuto Adjust is disabled

A full Auto Adjust determines actuator direction, spring direction, stroke, opening and closing times, control parameters and the I/P module offset.

Auto Adjust Display Sequence

DisplayFunction
RUN 10Saves the fully depressurized actuator position
RUN 20Saves the fully pressurized actuator position
RUN 30–32Measures opening and closing stroke times
RUN 40–49Determines the tolerance band and fast-control parameters
RUN 50–59Determines the precision-control parameters
RUN 200Auto Adjust is complete
COMPLETECalibration completed successfully

All Auto Adjust status messages other than RUN must be acknowledged by pressing ENTER.

Changing the Signal Direction

Use P2.3 ACTION to change the relationship between the input signal and the defined valve position.

Menu Procedure

  1. Enter configuration mode.
  2. Hold MODE + ENTER.
  3. Press ▲ or ▼ until P2._ SETPOINT appears.
  4. Release the buttons.
  5. Hold MODE and select P2.3 ACTION.
  6. Select DIRECT or REVERSE.
  7. Move to P2.8 EXIT.
  8. Select NV_SAVE.
  9. Hold ENTER until the countdown reaches 0.

The standard TZIDC/TZIDC-200 setpoint group contains P2.0 MIN_RGE, P2.1 MAX_RGE, P2.2 CHARACT, P2.3 ACTION and P2.8 EXIT.

DIRECT and REVERSE

Setting4 mA20 mA
DIRECTDefined position 0%Defined position 100%
REVERSEDefined position 100%Defined position 0%

When the valve has been configured so that 0% means closed:

  • DIRECT: 4 mA = closed; 20 mA = open
  • REVERSE: 4 mA = open; 20 mA = closed

ABB defines DIRECT as an increasing relationship between the analog setpoint and position, while REVERSE creates a decreasing relationship.

Important: P2.3 ACTION is not the actuator fail action. The valve’s position after loss of air or electrical power depends on the actuator spring arrangement, pneumatic module and tubing configuration.

Setpoint Range and Characterization

For standard 4–20 mA commissioning, retain:

ParameterRecommended Setting
P2.0 MIN_RGE4.0 mA
P2.1 MAX_RGE20.0 mA
P2.2 CHARACTLINEAR
P2.3 ACTIONDIRECT or REVERSE as required

The TZIDC also supports equal-percentage and user-defined characteristic curves. These should only be selected when required by the control-valve application.

Factory Reset

The original reset procedure must not be used without first placing the positioner in its safe position.

Correct Factory Reset Procedure

  1. Isolate the valve from the process.
  2. Enter configuration mode.
  3. Select parameter group P11._ FS/IP.
  4. Open P11.0 FAIL_POS.
  5. Hold ENTER until the countdown reaches 0 to activate the safe position.
  6. Select P11.1 FACT_SET.
  7. Select FS_LOAD.
  8. Hold ENTER until the countdown reaches 0.
  9. Wait until COMPLETE appears.
  10. Press ENTER to acknowledge.
  11. Check that the configured I/P module type matches the module physically installed.
  12. Return to P11.0 FAIL_POS and deactivate the safe position.
  13. Save the settings through EXIT → NV_SAVE.
  14. Reconfigure the actuator type and perform a new full Auto Adjust.

ABB prevents factory settings from being loaded unless FAIL_POS has first been activated. After resetting, the I/P module type must be checked because an incorrect setting may cause the actuator to move rapidly to an end position.

Do not use Factory Reset as a normal troubleshooting step. Use it only when the positioner is being installed on a different actuator or when the previous configuration is no longer usable.

Common Auto Adjust Errors

MessageMeaning and Checks
CALC_ERRPlausibility check failed. Check mounting, travel and pneumatic connections.
OUTOFRNGFeedback shaft exceeded its permitted sensor range. Correct the linkage or rotary coupling.
RNG_ERRThe feedback movement uses less than 10% of the available sensor range.
TIMEOUTControl parameters could not be determined within the permitted time. Check air pressure, friction, leakage and actuator speed.
SPR_ERRThe detected actuator spring direction does not match the configuration.
BREAKAuto Adjust was interrupted by the operator.

These messages are displayed when Auto Adjust cannot complete its mechanical or control-parameter checks.

Final Function Check

After successful calibration, verify:

Input SignalExpected Position with DIRECT*
4 mA0%
8 mA25%
12 mA50%
16 mA75%
20 mA100%

*Assuming a 4–20 mA full range, linear characterization and no split-range configuration.

Confirm that:

  • The valve moves in the correct direction.
  • The displayed position agrees with the mechanical valve position.
  • The valve reaches both end positions.
  • Movement is smooth and stable.
  • No active alarm or calibration error remains.
  • The positioner has returned to automatic control.

Quick Setup Sequence

▲ + ▼ → Press ENTER → Countdown 3–0 → P1.0 ACTUATOR → P1.2 FULL → P1.1 AUTO_ADJ → Hold ENTER → COMPLETE → P1.4 EXIT → NV_SAVE

Recent Posts

Facebook
Twitter
LinkedIn
Pinterest
Print
Picture of Will Don

Will Don

After earning my bachelor's degree in mechanical engineering from Zhejiang Normal University in 2008, l was fortunate enough to begin my career with Siemens, Fisher, and YTC, focusing on control valve accessories. Over the past dozen years, l've poured my heart and energy into understanding technology and fluid solutions for control valves.
Now, as the marketing director for THINKTANK, a trusted branch of the Taiwan STONE valve group, I can't help but feel proud of how far we've come.
Our knowledge isn't just reaching professionals like engineer and valve distributors; it's also inspiring the next generation of automation college students.
l genuinely hope you're enjoying our articles and finding them helpful. Your thoughts, questions, and feedback mean the world to me, so please don't hesitate to reach out to [email protected]. Whether you're a seasoned expert or just curious about the field, I'm here to connect, share, and learn together.

All Posts »

I am the author of this article, and also the CEO and marketing director of THINKTANK, with 15 years of experience in the industrial valve industry. If you have any questions, you can contact me at any time.

Contact Us

Just fill out your name, email address, and a brief description of your inquiry in this form. We will contact you within 24 hours.

Why are more and more international valve brands choosing THINKTANK for OEM service?

Brand is reputation, which not only requires high valve technology, but also great comercial support and fast response after-sales service and delivery time. They will not gamble their brand on an unknown product

Get an Instant Quote

Avoid your inquiry is delay response, please enter your WhatsApp/Wechat/Skype along with the message, so we can contact you at the very first time.

We will reply you within 24 hours. If for urgent case, please add WhatsApp: +86 185 1656 9221, or WeChat: +86 199 2125 0077. or call +86 189 5813 8289 directly. 

Get An Instant Quote

Joy Preview

Get An Instant Quote

We will reply you within 24 hours. If for urgent case, please add WhatsApp: +86 199 2125 0077, or WeChat: +86 199 2125 0077. Or call +86 189 5813 8289 directly. 

Direct to Control Valve Factory With Competitive Price & Reliable Quality

Joy Preview
Joy Preview

Get An Instant Quote

Just leave your name, email, and simple message or requirements, We will contact you within 1 hour.

WhatsApp: +86 199 2125 0077

Skype ID: sowell85

Wechat ID: +86 199 2125 0077