Control Valve Failure Modes

This post will discuss the various failure modes associated with control valves and how to detect them. We will look at the different types of failures that can occur, from the more common issues of poor calibration or stuck valves, to those more difficult-to-diagnose faults such as latching or coking. We'll also explore potential causes for each type of failure and how best to remedy them. Finally, we'll consider ways to better monitor control valves and keep them functioning correctly over time.
Table of Contents
    Add a header to begin generating the table of contents

    In the industrial process, the key stations have requirements for their emergency failure positions for control valves. It is necessary to ensure that the control valve is in a safe position under different failure issues. For example, in the case of loss of instrument air supply or loss of power, this post will tell you specifically about the different fail-safe modes.

    control valve failure modes

    The control valve has four options for fail-safe positions for emergency conditions.

    a.) Valve Fully Closed

    b.) Valve Fully Open

    c.) Valve in The Last Position

    d.) Valve Continues to Control

    For instrument air supply pressure loss or power loss, it is the bench-set setting spring range of the pneumatic actuator that drives the plug of the control valve to its failure-safe valve open or closed position.

    I. Instrument Air Supply (IAS) Pressure Loss

    a.) Valve fully closed

    For the reverse action of the control valve, the fail mode is air to open(ATO), which means the failure-safe position is the valve fully closed.

    air to open fail valve close
    Picture From Instrumentation Tools

    When the loaded instrument air pressure approaches 0 psig, the actuator’s bench-set range spring “drives” the valve plug to the valve closed position.

    Due to instrument air supply piping systems providing air power for a wide range of equipments in the field, so the decay of instrument air supply may action slowly, which will cause operation issues for control valves.

    In this case, it may be necessary to use a 3-way pilot switching valve to “predict” the eventual IAS loss and quickly drive the control valve to the failure position to eliminate the transient operational effects of slow decay.

    b.) Valve fully open

    For the direct action of the control valve, the fail mode is air to open(ATC), which means the failure-safe position is the valve fully open.

    When the loaded instrument air pressure approaches 0 psig, the actuator’s bench-set range spring “drives” the valve plug to the valve fully open position.

    To remove transitory effects, a technique similar to a. preceding may be used for ATC FO configurations for failure valve open control valves.

    c.) Valve in the last position

    This is accomplished by an air lockup valve, which is a two-way pilot switching valve. If the air set of the control circuit loses pressure, the air lockup valve will close and lock the air in the air chamber of the pneumatic actuator.

    If there is no air leakage, the control valve will remain in the last position. Such a loop is usually localized. Usually, a safety failure that holds the final position will have time-limited because the air chamber, tubing, or accessories instrument of control valves will cause an air leakage, which makes the lockup air in the pneumatic actuator volume gradually decreases, so the last position will tend to fully open or fully closed.

    valve at last position
    valve at the last position

    d.) Valve continues to control

    This is a specially designed engineered instrumentation system that can be accomplished in two different ways.

    1.) Adding a Backup Volume tank

    A capacity tank stores a limited supply of instrument air supply to maintain the regular operation of the control valve for a limited period of time, i.e., approximately one hour or more, designing the tank volume/capacity shall be according to the customer’s requirements.

    2.) Alternate Gas Supply

    A high-pressure cylinder with a backup gas, usually GN2, is stored on standby. If the instrument air supply pressure drops below 50 psig, the backup gas will take over the supply pneumatic control. The high pressure will allow several hours of continuous operation with enough time to recover from an emergency loss of IAS.

    valve continues to control
    valve continues to control

    This application is typically used for very critical operating conditions. Such loops are usually local and pneumatically controlled only; i.e., no electrical power is involved except for a low-pressure alarm switch.

    II. Loss of Electrical Power

    Protection against power loss is achieved indirectly through the use of a solenoid valve. In regular operation, the solenoid valve is energized; in the event of an emergency power failure, the solenoid valve is de-energized and jumps to the “on hold position.” The solenoid valve voltage can be selected as 24 VDC, 120 VAC, 220 VAC, etc.

    a.) Valve fully closed

    By blocking the load air to the actuator and venting the air in the actuator load chamber to the atmosphere (P = 0 psig), the actuator’s bench-set range spring drives the plug to close the valve. The solenoid valve is a 3-way type.

    valve fully closed
    valve fully closed

    b.) Valve fully open

    By blocking the load air to the actuator and venting the air in the actuator load chamber to the atmosphere (P = 0 psig), the actuator’s bench-set range spring drives the plug to open the valve. The solenoid valve accessories and tubing design are the same as case a.)

    c.) Valve in the last position

    A two-way solenoid valve accomplishes this failure-safe design. In the energized state, the solenoid valve port is open, and loading air passes through. In the powered-off state, the solenoid valve is closed, trapping air in the actuator’s loading chamber.

    loss of electrical power
    loss of electrical power

    Abbreviations of valve terms

    IAS: Instrument Air Supply
    FTC: Fail/failure to Close
    FTO: Fail/failure to Open
    FO: Fail/failure Open
    FC: Fail/failure Close
    S/SV: Solenoid Valve

    Solutions of pneumatic control valve Fail Position – Keep Valve at Last Position

    In industrial automation control, sometimes need pneumatic control valves should fail to keep at the last position, the following three solutions are to keep the valve failure at the last position for double-acting pneumatic control valve failure.

    Solution 1: the program is mainly composed of a pneumatic control valve, solenoid valve, valve positioner, air lockup valve, check valve, diaphragm pump pressure reducing valve, storage tank, etc.

    control valve work shop1
    control valve factory

    working principle

    When the control system air source fails (loss of instrument air supply), the air lockup valve (which acts in the opposite way to the air lockup valve ) automatically opens, the control of the solenoid valve air source is withdrawn, the solenoid valve slide valve reset under the action of the spring, one of the two solenoid valves exhaust, the other into the air, the one-way valve closed, the air source stored in the gas storage tank to the valve supply, so as to achieve the fully close or open valve. The conversion of fully closed or fully open can be achieved by adjusting the connection of the air controller.

    If you want to realize the valve to keep at the last position, assemble a pneumatic valve and change the pipeline connection, use the air lockup valve to directly control the valve, solenoid valve, check valve, and gas storage tank.

    Solution 2: if you want to achieve if loss of air source to ensure that the valve has a number of times the action, the control valve can be used in the following program.

    This program consists of a gas storage tank, check valve, blocking valve, shut-off valve, etc. Its working principle is as follows.

    steam control valves
    steam control valves

    When the gas source fails (loss of gas), the check valve closes, the blocking valve loses of gas, the slide valve in the blocking valve resets under the action of the spring, the gas circuit reversal, disconnect the system’s gas source pipeline, connected to the gas storage tank pipeline, the gas supply from the storage tank to the valve, to ensure that the valve has a number of actions to achieve the purpose of continuous control. Due to the limited capacity of the storage tank and the pressure of the gas source in the storage tank with the valve action decreases, can not use the storage tank for a long time to supply air to the valve. The capacity of the gas storage tank used in this program should be larger than the capacity of the general protection gas storage tank. This program in the case of a broken gas source, the number of valve actions, and the capacity of the storage tank.

    Solution 3: Pneumatic control valve between the positioner and the actuator in series with an air lockup valve and a two-way three-port solenoid valve.

    In the case of a gas break with air lockup valve to keep at the last position. in the case of a signal break, use the solenoid valve to keep at the last position. However, the solenoid valve must be interlocked with the positioner (set in the control program), which means if the positioner has a signal, the solenoid valve must have power, once the positioner loses signal, the solenoid valve must immediately power off.

    hart networks 4
    control valves with hart network

    Electric Control Valve Failure Modes

    For the electric control valve, when there is a loss of the signal, it can stay in any of the positions of fully open, fully closed, or held based on the setting of the control module, while when there is a loss of the power, it naturally stays in the failure position, or the electric actuator with reset device can also operate the valve position to fully open or fully closed.

    What are three common valve failures for diaphragm pneumatic globe control valves?

    There are three common failures for diaphragm pneumatic globe control valves, loss of air supply, loss of electric power, and loss of signal. Generally, when we select the right pneumatic control valves for application, we need to know whether the air to open or close the valve, which means selecting the failure-safe position.

    If the process requires the diaphragm pneumatic control valve (spring-turn) to open when loss of air supply, then choose the normally open type control valve.

    If requires the diaphragm pneumatic control valve (spring-turn) to close when loss of air supply, then choose the normally closed type control valve.

    But if the control system requires three common failures, namely, loss of air supply, loss of electric power, and loss of control signal at the same time, then the control valve needs to be configured with some accessories to form a protection system to achieve the control requirements, these accessories are mainly the air lockup valve, solenoid valve, gas tank, etc. The following are two modes of solutions for a single-acting pneumatic diaphragm control valve and a double-acting pneumatic control valve.

    I. Solution for Diaphragm pneumatic globe type control valve (Single acting, spring-return)

    control valve failure modes

    This program mainly consists of a diaphragm pneumatic control valve, an electric-pneumatic valve positioner, a loss of power comparator, a single electronically controlled solenoid reversing valve, an air lockup valve, limit switches, etc. Its working principle is as follows:

    1. Loss of air source

    When the control system air source failure, the air lockup valve automatically closes to lock the output signal pressure of the positioner in the diaphragm chamber of the pneumatic control valve, and the output signal pressure is balanced with the counter force generated by the actuator spring of control valve, and the valve position of the pneumatic control valve is maintained in the fault position. The air lockup valve should be set to start when it is slightly below the minimum value of the air source.

    2. power failure

    When the power supply of the control system fails, the loss of power comparator controls the output voltage disappears, the single electronically controlled solenoid-operated reversing valve loses power, the spool of the solenoid valve slides under the action of the reset spring, the solenoid valve reverses, the pressure of the membrane chamber of the air lockup valve is emptied, the lockup valve is closed, the output signal pressure of the positioner is locked in the membrane chamber of the pneumatic control valve, the output signal pressure is balanced with the counter force generated by the control valve spring, and the valve position of the pneumatic control valve is maintained in the fault position.

    3. Loss of control Signal

    When the control system signal failure is detected by the power loss comparator, the voltage signal of the single electronically controlled solenoid reversing valve is broken, the single electronically controlled solenoid reversing valve loses power, the slide valve inside the single electronically controlled solenoid reversing valve slides under the action of the reset spring, the solenoid valve reverses direction, the pressure of the membrane chamber of the pneumatic position-keeping valve is emptied, the pneumatic position-keeping valve is closed, the output signal pressure of the positioner is locked in the membrane chamber of the pneumatic control valve. The output signal pressure is balanced with the counter force generated by the control valve spring, and the valve position of the pneumatic control valve is maintained in the failure safe position.

    The position feedback signal is given by the limit switches or valve positioner.

    reliable control valves in china
    reliable control valves in china

    Three modes break protection when starting, the advantage of this program is system response is fast. The overall cost is relatively cheap.

    Disadvantages of this solution: the solenoid valve is charged for a long time, affecting the service life. With more accessories, installation and commissioning are more complicated, and valve position feedback needs to be equipped with separate limit switches, in the case of a hand wheel is more complicated.

    II.Solution for double-acting pneumatic control valve

    Cylinder Control Valves
    Cylinder Control Valves

    This program mainly consists of a control valve, pneumatic controller, valve positioner, air lockup valve, check valve, pressure reducing valve, gas storage tank, etc. Its working principle is as follows.

    When the control system air source failure, the self-locking valve automatically opens, the control air source of the pneumatic controller is withdrawn, the slide valve of the pneumatic controller is reset under the action of the spring, one of the two air-controlled reversing valves exhausts, the other feeds, the check valve closes, and the air source is supplied to the valve by the air source stored in the gas storage tank, thus realizing the full close or open valve. The conversion of fully closed or fully open can be achieved by adjusting the connection of the pneumatic controller.

    If you want to achieve the valve to keep at the last position, install an air lockup valve and change the tubing connection, use the air lockup valve to control the valve directly, there is no need pneumatic controller, check valve, and storage tank.

    If you want to make sure the number of times the action of the control valve is when loss of air supply, the following program can be used.

    This program consists of a gas storage tank, check valve, blocking valve, stop valve, etc. Its working principle is as follows.

    When the air source failure, the check valve closes, the blocking valve loses air, the spool in the blocking valve is reset under the action of the spring, the gas circuit reverses, disconnects the system’s air tubing, connects the gas storage tank pipeline, the gas supply from the storage tank to the valve, to ensure that the valve has a number of times the action, to achieve the purpose of continuous control. Due to the limited capacity of the storage tank, and the pressure of the gas source in the storage tank with the valve action decreases, can not use the storage tank for a long time to supply air to the valve. The capacity of the gas storage tank used in this program should be larger than the capacity of the general protection gas storage tank. The number of valve actions in this program is related to the capacity of the storage tank when the gas source is disconnected.

    How do you troubleshoot a control valve?

    control valve troubleshooting pDF

    Summary

    This post provides an overview of the different failure modes associated with control valves and how to detect them. Common issues such as poor calibration or stuck valves can be easily identified, while more difficult-to-diagnose faults need to control valve experts to analyze and solve. THINKTANK is a well-known brand of control valves in China, you can completely trust us to help you sizing and select the right control valves for your applications and projects. Contact us today you will get a free consultation.

    Facebook
    Twitter
    LinkedIn
    Pinterest
    Print
    Picture of Will Don

    Will Don

    After earning my bachelor's degree in mechanical engineering from Zhejiang Normal University in 2008, l was fortunate enough to begin my career with Siemens, Fisher, and YTC, focusing on control valve accessories. Over the past dozen years, l've poured my heart and energy into understanding technology and fluid solutions for control valves.
    Now, as the marketing director for THINKTANK, a trusted branch of the Taiwan STONE valve group, I can't help butf eel proud of how far we've come. Our knowledge isn't just reaching professionals like engineer and valve distributors; it's also inspiring the next generation of automation college students.
    l genuinely hope you're enjoying our articles and finding them helpful.Your thoughts, questions, and feedback mean the world to me, so please don't hesitate to reach out to marketing[at]cncontrolvalve.com. Whether you're a seasoned expert or just curious about the field, I'm here to connect, share, and learn together.

    All Posts »

    I am the author of this article, and also the CEO and marketing director of THINKTANK, with 15 years of experience in the industrial valve industry. If you have any questions, you can contact me at any time.

    The Latest News
    dn25 pn16 wcb pcv (1)

    Pneumatic Single-Seat Globe Control Valves PCV DN25 PN16

    DN25 PN16 A216GR.WCB PCV (THINKTANK)
    Read More
    heat shutdown on off valve

    Valvula shut off com atuador fusível

    A válvula shut-off com atuador fusível é um dispositivo utilizado para controlar automaticamente o fluxo de fluidos em tubulações, especialmente em situações de emergência ou ...
    Read More
    c95500 nickel aluminum bronze control valve factory thinktank

    Engineering Case Studies of C95500 Nickel Aluminum Bronze Control Valves

    In modern industry, the choice of control valves is critical for ensuring the reliability, efficiency, and safety of processes. As a leading manufacturer of C95500 ...
    Read More
    atex ped certificate

    Congratulations to THINKTANK Achieve ATEX and PED Certificates For Fusible Link Safety Valve and Breather Valve Series

    As the co-founder of THINKTANK, it is with a profound sense of pride and humble excitement that I share a milestone that marks a significant ...
    Read More
    Self Operated Pressure Regulator

    The 18inch Self-Operated Pressure Regulator Super Duplex 2507

    The DN450(18″) 150LB self-operated pressure regulator is made from super duplex 2507 material. This pressure regulator is specifically designed for seawater desalination applications, where exceptional ...
    Read More
    canary bridge data centre phase 39

    THINKTANK Delivers 898 Ball Valves Ahead of Schedule to Malaysia

    THINKTANK has advanced the delivery of 898 ball valves to a Malaysian client, with all valves undergoing 100% rigorous testing to ensure a 100% qualification ...
    Read More
    thinktank control valve factory

    Top 10 Industrial Valve Manufacturers in China 2024

    This article is not just aimed at keeping international brands informed about the latest developments in the Chinese industrial valve industry but also serves industrial ...
    Read More
    flow conversion table

    Fluid Flow Rate Conversion Chart

    Flow rate measures the volume of fluid that passes through a specific point within a given time frame, commonly used units include cubic meters per ...
    Read More
    fire safey valve post

    Celebrating THINKTANK’s Milestone: Leading the Way in Fire Safety Valves

    Recently at THINKTANK, we had the privilege of publishing an article in “Tank Storage Magazine”(Spring 2024 Page 82) on fusible link fire safety valves, a ...
    Read More

    Contact Us

    With expertise in valves and rich experience in the oil&gas, chemical industry, textile mills, power plants, and sugar mills. THINKTANK has become the premier manufacturer of next-generation precision control valves.

    With a customer base that includes over 42 of the world’s leading engineering&contractors and international valve brands, THINKTANK Valves offers cost-effective valves that help our customers achieve automated process control without paying high prices.

    Why are more and more international valve brands choosing THINKTANK for OEM service?

    Brand is reputation, which not only requires high valve technology, but also great comercial support and fast response after-sales service and delivery time. They will not gamble their brand on an unknown product

    Get An Instant Quote

    Joy Preview

    Focused on Control Valves & Self-Operated Pressure Regulators For Over 30 Years

    A Good Partner Is A Lasting And Effective Investment

    Get An Instant Quote

    Direct to Control Valve Factory With Competitive Price & Reliable Quality

    Joy Preview
    Joy Preview

    Get An Instant Quote

    Just leave your name, email, and simple message or requirements, We will contact you within 1 hour.

    WhatsApp: +86 185 1656 9221

    Skype ID: sowell85

    Wechat ID: +86 199 2125 0077